Phosphonate removal from discharged circulating cooling water using iron-carbon micro-electrolysis

  • Zhen Zhou*
  • , Weimin Qiao
  • , Yangbo Lin
  • , Xuelian Shen
  • , Dalong Hu
  • , Jianqiao Zhang
  • , Lu Man Jiang
  • , Luochun Wang
  • *Corresponding author for this work

Research output: Contribution to journalArticlepeer-review

26 Scopus citations

Abstract

Phosphonate is a commonly used corrosion and scale inhibitor for a circulating cooling water (CCW) system. Its discharge could cause eutrophication of receiving waters. The iron-carbon (Fe/C) microelectrolysis technology was used to degrade and remove phosphonate from discharged CCW. The influences of initial pH, Fe/C ratio (FCR) and temperature on phosphonate removal were investigated in a series of batch tests and optimized by response surface methodology. The quadratic model of phosphonate removal was obtained with satisfactory degrees of fitness. The optimum conditions with total phosphorus removal efficiency of 95% were obtained at pH 7.0, FCR of 1.25, and temperature of 45°C. The phosphonate removal mechanisms were also studied. Phosphonate removal occurred predominantly via two consecutive reactive phases: the degradation of phosphonate complexes (Ca-phosphonate) and the precipitation of Fe/C micro-electrolysis products (PO43-, Ca2+ and Fe3+).

Original languageEnglish
Pages (from-to)524-532
Number of pages9
JournalWater Science and Technology
Volume70
Issue number3
DOIs
StatePublished - 2014
Externally publishedYes

Keywords

  • Circulating cooling water
  • Iron-carbon micro-electrolysis
  • Phosphonate
  • Response surface methodology

Fingerprint

Dive into the research topics of 'Phosphonate removal from discharged circulating cooling water using iron-carbon micro-electrolysis'. Together they form a unique fingerprint.

Cite this